Pump Affinity Laws Calculator
Scale a known pump duty point to a new speed or a trimmed impeller diameter. Flow follows the ratio, head follows its square, power follows its cube.
Enter a known duty point on the pump curve, then the speed and/or impeller diameter before and after the change.
Speed ratio N₂/N₁ = 0.8. Flow scales with the ratio, head with its square, power with its cube.
Formula
| Symbol | Meaning | Unit |
|---|---|---|
| Q₁, H₁, P₁ | Flow, head and shaft power at the known duty point | m³/h, m, kW |
| Q₂, H₂, P₂ | Flow, head and shaft power at the new speed or diameter | m³/h, m, kW |
| N₁, N₂ | Pump speed before and after the change | rpm |
| D₁, D₂ | Impeller diameter before and after the change | mm |
The speed laws apply to the same pump and impeller at a different speed; the diameter laws apply to the same pump at the same speed with the impeller trimmed. When both change at once, multiply the two ratios: , and likewise with the square for head and the cube for power.
Worked examples
Example 1 — SI: speed 2900 → 2320 rpm
- Duty point: , , at
- Speed ratio:
- Flow:
- Head:
- Power:
Slowing the pump by 20% cuts the power almost in half — that cubic relation is why variable-speed drives save so much energy.
Example 2 — US: speed 1750 → 1400 rpm
- Duty point: , , at
- Speed ratio:
- Flow:
- Head:
- Power:
The laws are pure ratios, so the units do not matter — the same 0.8 ratio works in gpm and feet as in m³/h and metres.
Example 3 — Impeller trim: 200 → 180 mm
- Duty point: , , ; impeller trimmed to
- Diameter ratio:
- Flow:
- Head:
- Power:
A 10% trim takes about 27% off the power. Trimming is a one-way, permanent change — unlike a speed change, you cannot trim the impeller back.
Assumptions and limits
- Same pump, same liquid. The laws scale one duty point of one pump. They do not compare different pumps, and they assume the liquid does not change.
- Efficiency is assumed constant — and that is the weak point. Real efficiency shifts when the speed or diameter changes. For speed changes beyond about ±30% or diameter trims beyond 20–25%, the efficiency change is no longer negligible and the laws become a rough estimate. The calculator warns you when you go past those ranges.
- The scaled point is not the new operating point. The laws move the pump curve; the system curve does not move. The pump will settle where the scaled pump curve meets the system curve, which is a different flow from the scaled duty point — check it with the operating point calculator.
- Diameter laws assume geometric similarity. A small trim of the same impeller is close enough. A large trim changes the impeller shape and the clearances, and the laws drift.
- Speed changes assume the motor can run there. Check the motor’s speed range, cooling at low speed, and any resonance or vibration limits before relying on a large speed change.
Next step
The scaled point is not the new operating point until it is checked against the system curve: Pump operating point calculator
Once you know the new operating point, work out what it costs to run with the pump energy cost calculator.
FAQ
Why does power change with the cube of the speed?
Power is flow times head (times density and gravity). Flow scales with speed, head scales with speed squared, so their product — power — scales with speed cubed. That is why a 20% speed cut halves the power, and why running a pump a little slower saves a lot of energy.
Can I use the affinity laws to predict the new operating flow?
No — not directly. The laws tell you where one point on the pump curve moves to. The pump will run where the whole scaled pump curve meets the system curve, and that flow is different from the scaled duty point. Use the operating point calculator with the scaled curve to find the real new operating point.
Is trimming the impeller the same as slowing the pump down?
The maths looks the same — both use the same ratios — but they are different changes. A speed change (for example with a VFD) is reversible and adjustable; a trim is a permanent machining of the impeller. A trim also changes clearances and can hurt efficiency more than the same speed change would.
How far can I trim an impeller?
Manufacturers usually allow trims up to about 20–25% of the original diameter; beyond that, efficiency drops off and the affinity laws stop being reliable. The calculator warns you past a 25% trim. Check the manufacturer's minimum impeller diameter for your pump — trimming past it is not allowed.
Do the affinity laws work for positive displacement pumps?
No. They apply to centrifugal (rotodynamic) pumps, where head comes from the impeller throwing liquid outwards. A positive displacement pump delivers a fixed volume per revolution, so its flow scales with speed but its head is set by the system, not by the speed.
Sources
- MEPFlow, "Pump Affinity Laws" — speed-law examples: 100 GPM/40 ft/2 kW at 80% speed, and 600 gpm/55 ft/18.5 hp at 1750 → 1400 rpm
- Firgelli, "Pump Affinity Laws Calculator" — diameter laws and the 20–25% trim accuracy limit
- Pump operating point calculator on this site — check the scaled point against the system curve
For preliminary estimates only. Verify against manufacturer data and the governing standard before purchase or installation.