pumpcalc

Pump Operating Point Calculator

Find the flow and head where your pump will actually run: fit a curve through three points from the manufacturer’s pump curve, describe the system with a static head and a resistance coefficient, and solve for the intersection.

Units:

Enter three points from the pump curve — the shutoff point (flow 0) and two more points from the manufacturer's curve. The calculator fits a parabola through them and finds where it meets your system curve.

Usually the shutoff point: flow 0.
Shutoff head at flow 0.

Flow is in m³/h and head in m — pump curves are published in m³/h or gpm, and the fit is done in those working units.

Vertical lift the pump must overcome, before any friction.
System resistance K:
Friction loss (not static head) at the reference flow below.
The flow the friction head above was calculated at.

K = 0.001563 m/(m³/h)²

Fitted pump curve: H = 50 + 0.025·Q + -0.0025·Q² (m, Q in m³/h)

Operating flow
95.95 m³/h
Operating head
29.38 m

Next step: Send 95.95 m³/h at 29.38 m to the pump power calculator →

Formula

Hpump(Q)=a+bQ+cQ2H_{\text{pump}}(Q) = a + bQ + cQ^2

Hsys(Q)=Hstatic+KQ2K=hfQ2H_{\text{sys}}(Q) = H_{\text{static}} + K Q^2 \qquad K = \frac{h_f}{Q^2}

(c−K)Q2+bQ+(a−Hstatic)=0(c - K) Q^2 + bQ + (a - H_{\text{static}}) = 0

SymbolMeaningUnit
H_pump(Q)Pump head at flow Q, fitted as a parabolam
a, b, cFitted coefficients; a is the shutoff head (head at Q = 0)m, m/(m³/h), m/(m³/h)²
QVolumetric flow ratem³/h
H_sys(Q)System head at flow Qm
H_staticStatic head: the lift the pump must overcome before any frictionm
KSystem resistance coefficient, K = h_f / Q²m/(m³/h)²
h_fFriction head at a reference flowm

Three points from the pump curve determine the parabola H=a+bQ+cQ2H = a + bQ + cQ^2 exactly — the shutoff point (0,a)(0, a) fixes aa, and the other two points fix bb and cc. The system curve is a parabola too: the static head plus a friction term that grows with the square of the flow. Setting the two equal gives a quadratic equation; its smallest positive root is the operating flow, and either curve gives the operating head.

Worked examples

Example 1 — SI: pump points (0, 50), (40, 47), (80, 36) m

The operating flow sits beyond the highest fitted point (80 m³/h), so check it against the real pump curve — the fit is an extrapolation there.

Example 2 — US: pump points (0, 150), (200, 140), (400, 110) ft

Same calculation, same method — only the units change, because the fit and the system curve use one consistent set of flow and head units throughout.

Assumptions and limits

Next step

Got an operating point? Size the motor for it — send the flow and head to the power calculator: Pump power calculator

If you change the pump speed or trim the impeller, the curve moves — use the pump affinity laws calculator to scale the duty point first, then check the scaled point against the system curve here.

FAQ

What three points should I pick from the pump curve?

The shutoff point (flow 0, shutoff head) and two more points spread across the range you expect to run in — for example the best-efficiency point and a point near the maximum expected flow. Points bunched together make the fit unreliable, and an operating point outside the range they cover is an extrapolation, so check it against the real curve.

How do I get the system resistance K?

From any known friction loss: K = h_f / Q². If you know the system loses 10 m of head to friction at 80 m³/h, K = 10 / 80² = 0.0015625 m/(m³/h)². You can work out the friction loss with the total dynamic head calculator, then enter the loss and the flow here and the calculator computes K for you.

What does "shutoff head is below the static head" mean?

The pump at zero flow produces its shutoff head — the most head it can ever make. If that is less than the static lift the system demands, the pump cannot push any liquid up at all: flow is zero and there is no operating point. You need a pump with a higher shutoff head or a lower static lift.

Why are there two roots, and which one is the operating point?

Two parabolas can cross twice. The smaller positive root is the stable operating point a centrifugal pump settles at. The larger root, when it exists, is an unstable crossing the pump will not stay at — the calculator takes the smaller one.

My operating point is outside the fitted range. Is it wrong?

Not necessarily wrong, but not verified either. The parabola is only guaranteed to pass through the three points you gave it; beyond them it is a guess. In the SI worked example the operating point (96 m³/h) sits beyond the highest fitted point (80 m³/h) — treat that as a warning to check the real curve, or re-fit with points that bracket 96 m³/h.

Sources

For preliminary estimates only. Verify against manufacturer data and the governing standard before purchase or installation.