Control Valve Sizing Calculator (Liquid)

Find the flow coefficient a liquid control valve needs — required Kv and Cv — from flow, upstream and downstream pressure, and the valve’s liquid pressure recovery factor, with a choked-flow check per IEC 60534-2-1. Free, no login.

Units:
Absolute pressure upstream of the valve, not gauge.
Absolute pressure downstream of the valve, not gauge.
1.0 for water. SG = liquid density / water density.
Vapour pressure below is filled in from the water table at this temperature.
From the water table at the temperature above.
From the valve manufacturer. Typical values: globe/single-seat 0.90, ball and butterfly 0.65.

Pressure drop 2 bar is below the choked drop 4.842 bar — flow is not choked, and the valve is sized on the full drop.

Required Kv
7.071
Sized on the full drop 2 bar.
Required Cv
8.174
F_F = 0.9571

Formula

Kv=QSGΔpsizingCv=1.156×KvK_v = Q \sqrt{\frac{SG}{\Delta p_{sizing}}} \qquad C_v = 1.156 \times K_v

FF=0.96−0.28pvpcΔpchoked=FL2(p1−FFpv)F_F = 0.96 - 0.28\sqrt{\frac{p_v}{p_c}} \qquad \Delta p_{choked} = F_L^2 (p_1 - F_F p_v)

SymbolMeaningUnit
KvRequired metric flow coefficientm³/h at 1 bar drop
CvRequired US flow coefficientUS gpm at 1 psi drop
QFlow ratem³/h
SGSpecific gravity of the liquid—
ΔpPressure drop across the valve, p₁ − p₂bar
Δp_chokedChoked (maximum effective) pressure dropbar
p₁, p₂Upstream and downstream absolute pressurebar
p_vVapour pressure at the flowing temperaturebar
p_cLiquid critical pressure (water: 220.6 bar)bar
F_FLiquid critical pressure ratio factor—
F_LLiquid pressure recovery factor (valve type)—

Kv is defined in m³/h at 1 bar drop, so this calculator works in m³/h and bar internally (US inputs are converted first). If the actual drop Δp reaches the choked drop Δp_choked, the flow is choked: the vena contracta pressure has fallen to vapour pressure, the liquid starts to flash, and a larger drop cannot push more flow through. In that case the sizing drop Δp_sizing is the choked drop, not the full drop — and the valve is at risk of cavitation. Enter the water temperature and the calculator fills in vapour pressure from the water table; override it for another liquid.

Worked examples

Example 1 — SI: non-choked, water at 20 °C

Example 2 — SI: choked, same valve, lower downstream pressure

Note the required Kv is smaller when choked: the valve can only use 4.84 bar of the 5.5 bar drop. The remaining drop is wasted across the valve and the flashing liquid is likely to cavitate — check the valve and the downstream piping, and consider a valve with a higher FLF_L or a larger drop taken elsewhere in the system.

Example 3 — US: 44 gpm at 87 psi(a)

Assumptions and limits

Next step

Need the coefficient in the other unit, or the flow a valve with a known Kv passes? Convert and check it here: Kv to Cv converter

Choked flow means the valve may cavitate — the same vapour-pressure check sits behind the NPSH available calculator, which works out whether a pump inlet has enough suction head to avoid cavitation.

FAQ

What is choked flow in a control valve?

When the pressure at the valve’s narrowest point (the vena contracta) falls to the liquid’s vapour pressure, the liquid starts to flash into vapour and the flow stops increasing, however much larger the drop across the valve becomes. The maximum effective drop is Δp_choked = F_L²(p₁ − F_F·p_v). A choked valve is sized on that drop, not the full drop — and it is likely to cavitate, so a choked result is a warning to change the selection.

What F_L should I use if the manufacturer does not give one?

Use the typical values as a starting point: about 0.90 for a globe or single-seat valve, about 0.6–0.7 for a ball or butterfly valve (this calculator uses 0.65). But F_L depends on the valve’s trim and the manufacturer’s test data — for a final selection, always use the manufacturer’s published F_L for the exact valve and trim.

Do I enter absolute or gauge pressure?

Absolute pressure, both upstream and downstream. The choked-flow check compares pressures with vapour pressure, which is an absolute quantity — using gauge pressure understates p₁ and gives a wrong (usually too small) choked drop. At sea level, add about 1.013 bar (14.7 psi) to a gauge reading to get absolute pressure.

Kv or Cv — which one do I need?

Kv is the metric coefficient (m³/h at 1 bar drop) and Cv is the US coefficient (US gpm at 1 psi drop); they describe the same valve, Cv = 1.156 × Kv. European valve datasheets quote Kv, US datasheets quote Cv — this calculator gives you both. The Kv to Cv converter on this site converts between them and works out flow from a known coefficient.

Does this calculator pick a valve size for me?

No. It gives the required flow coefficient — the Kv (or Cv) the valve must provide at the duty point. Valve size and model come from the manufacturer’s data: pick a valve whose rated Kv at a sensible travel, typically 60–80% open, covers the required Kv, then check the manufacturer’s noise and cavitation data for the service.

Sources

For preliminary estimates only. Verify against manufacturer data and the governing standard before purchase or installation.