pumpcalc

DN to NPS Pipe Size Conversion

Convert between DN (Diameter Nominal) and NPS (Nominal Pipe Size) and look up the pipe outside diameter in millimetres and inches. Pick a size on either side — the other follows.

Pick either side — the other follows. Outside diameters are the ASME series.

Outside diameter
114.3 mm
NPS 4 · 4.5 in

8 of 14 rows were checked against a source; the other 6 still need a second source check. Rows marked “to confirm” show the best available values — verify them before ordering.

DNNPSOD (mm)OD (in)Status
DN15NPS 1/221.30.8386Checked
DN20NPS 3/426.71.051Checked
DN25NPS 133.41.315Checked
DN32NPS 1-1/442.21.661to confirm
DN40NPS 1-1/248.31.902Checked
DN50NPS 260.32.374Checked
DN65NPS 2-1/2732.874to confirm
DN80NPS 388.93.5Checked
DN100NPS 4114.34.5Checked
DN125NPS 5141.35.563to confirm
DN150NPS 6168.36.626Checked
DN200NPS 8219.18.626to confirm
DN250NPS 1027310.75to confirm
DN300NPS 12323.912.75to confirm

Formula

There is no formula for DN to NPS. The correspondence is a nominal-size table fixed by ISO 6708 and ASME B36.10 — a lookup, not a calculation. The only arithmetic on this page is the unit conversion for the outside diameter:

ODin=ODmm25.41 in=25.4 mmOD_{\text{in}} = \frac{OD_{\text{mm}}}{25.4} \qquad 1\ \text{in} = 25.4\ \text{mm}

SymbolMeaningUnit
OD (mm)Pipe outside diametermm
OD (in)Pipe outside diameterin

DN and NPS are both nominal designations: neither one is a measured diameter. DN100 pipe does not measure 100 mm across — its outside diameter is 114.3 mm. The table above is what connects the two systems.

Worked examples

Example 1 — DN100 to NPS

A DN100 pipe has a 114.3 mm (4.5 in) outside diameter.

Example 2 — DN50 to NPS

The nominal NPS 2 outside diameter is 2382\frac{3}{8} in (2.375 in). The 0.001 in gap is rounding — the millimetre figure is rounded to 0.1 mm.

Example 3 — NPS 6 to DN

For NPS 4 and above, DN is normally 25 times the NPS number (6 × 25 = 150). Below NPS 4 the pairs are fixed by convention, not by multiplication — NPS 2 is DN50, not DN50 by any rule you can compute.

Assumptions and limits

Next step

Matching a DN pipe to an NPS flange? Check whether the two flanges actually bolt together: Flange compatibility checker

FAQ

Are DN and NPS the same thing?

No. DN (Diameter Nominal) is the metric size system from ISO 6708; NPS (Nominal Pipe Size) is the inch-based system from ASME B36.10. The two happen to align row by row — DN100 is NPS 4, DN50 is NPS 2 — but the numbers are not interchangeable: DN100 is not NPS 100, and you cannot convert one to the other by multiplying. Use the table.

Why does the outside diameter matter more than the nominal size?

Because fittings, flanges and couplings mate on the outside diameter, not on the nominal size. Two pipes with the same DN have the same OD whatever their wall thickness, so the OD is the dimension that decides whether a fitting fits. The nominal size is only a label for ordering and referencing.

Why do EN and ASME outside diameters differ on some sizes?

The two systems standardised pipe independently, so a few sizes ended up with different ODs. This table uses the ASME series. In the EN series, DN20 is 26.9 mm (not 26.7 mm) and DN25 is 33.7 mm (not 33.4 mm). On a mixed-standard project, confirm which series the pipe, fittings and flanges all follow.

What does “to confirm” mean on some table rows?

It means that row has not yet been checked against a second source. 8 of the 14 rows were verified against a published conversion table; the other 6 — DN32, DN65, DN125, DN200, DN250 and DN300 — still need that second check. The values shown are the best available, and the converter works for them, but verify them against the standard or a supplier catalogue before ordering.

What if my size is not in the table?

The table covers DN15 to DN300 (NPS 1/2 to NPS 12), the sizes in ISO 6708 and ASME B36.10 up to NPS 12. For larger sizes, look them up in the standard itself: above NPS 14 the outside diameter in inches equals the NPS number, so DN350 is NPS 14 with a 14 in (355.6 mm) OD.

Sources

For preliminary estimates only. Verify against manufacturer data and the governing standard before purchase or installation.

Reviewed by pumpcalc · Last updated 2026-11-17