pumpcalc

Pump Power Calculator with Motor Sizing

Calculate a pump’s hydraulic and shaft power from flow, head and efficiency — then pick the next IEC standard motor size, with a margin factor you can adjust. Free, no login.

Units:
Pump efficiency from the pump curve, not motor or VFD efficiency.
Common practice, adjust to your specification.

Margin-adjusted power: 19.46 kW × 1.25 = 24.32 kW — the motor must cover at least this much.

Hydraulic power
13.62 kW
= 18.27 hp
Shaft power
19.46 kW
= 26.09 hp
Recommended motor size (next IEC rating)
30 kW
= 40.23 hp

Formula

Ph=ρgQHPs=PhηP_h = \rho g Q H \qquad P_s = \frac{P_h}{\eta}

US shortcut: Ps(hp)=Q(gpm)×H(ft)×SG3960×ηP_s(\text{hp}) = \frac{Q(\text{gpm}) \times H(\text{ft}) \times \text{SG}}{3960 \times \eta}

SymbolMeaningUnit
P_hHydraulic (water) powerkW
P_sShaft powerkW
ρLiquid densitykg/m³
gStandard gravity, 9.80665 m/s²m/s²
QFlow ratem³/s
HHeadm
ηPump efficiency (as a fraction)—

Hydraulic power is the power actually given to the liquid. Shaft power is what the motor must deliver, so it is larger — the pump’s inefficiency is paid for at the shaft. The motor is then sized above the shaft power by a margin factor, rounded up to the next IEC standard rating.

Worked examples

Example 1 — SI: 100 m³/h at 50 m head

Example 2 — US: 500 gpm at 100 ft head

The US shortcut gives 18.04 hp, while the exact SI calculation gives 18.06 hp — a 0.13% difference, because 3960 is a rounded constant. This calculator uses the exact SI calculation, so it shows 18.06 hp for these inputs.

Assumptions and limits

Next step

Power sorted? Check the pump has enough NPSH available at this duty point: NPSH calculator

FAQ

Why does the US shortcut (3960) differ slightly from the exact value?

The 3960 constant is a rounded combination of unit conversions (gpm to ft³/s, ft to m, hp to watts) and standard gravity. The exact SI calculation for 500 gpm at 100 ft, SG 1.0 and 70% efficiency gives 18.06 hp, while the shortcut gives 18.04 hp — a 0.13% difference. Either is fine for sizing; this calculator uses the exact calculation.

What efficiency should I enter?

The pump efficiency at the duty point, from the pump curve or datasheet — typically 50–85% for centrifugal pumps. Do not enter motor efficiency or VFD efficiency: shaft power is what the motor must deliver, and motor and VFD losses are separate and come after it.

What is the margin factor?

A safety margin applied to shaft power before picking a motor size, so the motor is not run at its rated limit. The defaults (1.25 up to 22 kW, 1.15 from 22 to 55 kW, 1.10 above 55 kW) are common practice, not a verified standard requirement — they are often attributed to API 610, but no citable public source for that was found, and KSB notes the margin may be specified by the buyer or per ISO 9905, 5199 or 9908. Change the factor to match your specification.

What if the required power is above 315 kW?

315 kW is the largest rating in the IEC 60072-1 series used here. The calculator shows 315 kW and warns you — a larger frame, a special motor, or a different pump selection is needed. Talk to the motor manufacturer.

Does this calculator include motor or VFD efficiency?

No. It gives hydraulic power and shaft power. Electrical input power is shaft power divided by motor efficiency (and by VFD efficiency, if one is fitted) — that is the number to use for running-cost estimates.

Sources

For preliminary estimates only. Verify against manufacturer data and the governing standard before purchase or installation.